15kV Switch and Transformer Preventative Maintenance
Closed October 5, 2026closed · Maryland
This bid is for preventative maintenance of electrical switches, transformers, and 480V equipment at the University of Maryland, Baltimore County, 1000 Hilltop Circle, Baltimore, MD 21250.
This bid has closed.
Buyers often post the same work again. Set an alert below and we will email you when a similar Maryland bid is posted.
What the job is
Equipment: Three-year schedule covering 34 switches rated 15kV, 13 transformers rated 13.2kV/480V (225–3,000kVA; liquid-filled and dry-type), and 480V panels with 10 main breakers and 92 distribution breakers.
Transformers: Visual/mechanical inspections, turns ratio, insulation resistance and power factor testing, plus heater/fan checks where applicable. Oil sampling excluded.
Switches and fuses: Inspect, exercise, clean and lubricate; perform insulation resistance, contact resistance, AC overpotential, and fuse/holder resistance tests.
480V equipment: Inspect panels, connections and insulators; test insulation and connection/contact resistance, charging mechanisms, and shunt-trip/close-coil pickup voltage. Secondary current testing only.
Standards and staffing: Follow manufacturer specifications, NETA and NFPA 70B/70E. Maryland Master Electrical License and five years’ relevant experience required; certified testing technicians with a NETA Level 2 or higher crew leader.
Outages and reports: Coordinate shutdowns with campus staff; supply lockout devices and protective grounds. Provide written test results and repair recommendations; quote replacement parts separately.
Pricing: Provide fully loaded weekday and evening/weekend/holiday hourly rates and identify other charges for a three-year term with two optional one-year renewals.