Tower: Approximately 152 feet tall with a 500,000-gallon capacity; include all labor, materials, equipment, mobilization, and cleanup.
Due
December 8, 2026
18 days left
Location
Maryland
Posted on
Maryland eMMA
Notice ID
BPM059661
Please quote interior wet chamber recoating of the 500,000-gallon Wor-Wic Water Tower in Salisbury, Wicomico County, Maryland.
Tower: About 152 feet tall, 500,000-gallon capacity; include all labor, materials, equipment, mobilization and cleanup.
Surface prep: Remove existing wet chamber coating, including piping and seams, by abrasive blasting to SSPC-SP 10/NACE No. 2 with at least a 1.5-mil surface profile.
Coating: Tnemec Series 93-H2O Hydro-Zinc primer at 2.5 to 3.5 mils, Series 21 Epoxoline stripe coat, and Series 21 Epoxoline finish in two coats at 16 to 20 mils total. Must meet AWWA D102 and ANSI/NSF 61.
Safety: OSHA-compliant confined space entry plan, ventilation, manufacturer coordination, coating thickness checks and holiday testing.
Disinfection: After the coating fully cures, disinfect the wet chamber per AWWA C652 before filling.
Warranty: Minimum two-year materials and workmanship warranty.
Please confirm availability and send your quote by December 8, 2026.
What it takes to win this job
No close past price for this exact job. We found fewer than 3 past awards for this same work, which is too few to give a fair price.
Price it from your own costs. Ask the buyer what they paid the last time they bought this.
To win it, you need
Surface preparation: Blast off existing wet chamber coating, including piping and seams, to SSPC-SP 10/NACE No. 2 with at least a 1.5-mil surface profile.
Required coatings: Use Tnemec Series 93-H2O Hydro-Zinc primer at 2.5, 3.5 mils dry thickness, Series 21 Epoxoline stripe coat, and two Series 21 Epoxoline finish coats totaling 16, 20 mils dry thickness, meeting AWWA D102 and ANSI/NSF 61.
Safety and testing: Provide an OSHA-compliant confined space entry plan, ventilation, manufacturer coordination, coating thickness checks, and testing for coating gaps.
Disinfection and warranty: After full cure, disinfect per AWWA C652 before filling and provide at least a two-year materials and workmanship warranty.
Quote deadline: Quotes are due December 8, 2026.
The original documents
Deadline: December 8, 2026
See the original on emma.maryland.gov
Bidding it yourself? Get the full package and submit on Maryland eMMA before December 8, 2026.
What they need
Surface preparationRemove existing wet chamber coating, including piping and seams, by abrasive blasting to SSPC-SP 10/NACE No. 2 with a minimum 1.5-mil surface profile.
Coating systemTnemec Series 93-H2O Hydro-Zinc primer at 2.5–3.5 mils DFT, Series 21 Epoxoline stripe coat, and Series 21 Epoxoline finish at 16–20 mils DFT in two coats. Coatings must comply with AWWA D102 and ANSI/NSF 61.
Safety and qualityProvide an OSHA-compliant confined space entry plan, ventilation, manufacturer coordination, coating thickness verification, and holiday testing.
DisinfectionAfter full coating cure, disinfect the wet chamber per AWWA C652 before filling. Include a minimum two-year materials and workmanship warranty.
Other recent awards in this industry in Maryland
Recent federal contract awards (federal buyers) in the same industry in Maryland, from USAspending.gov. These are other jobs, not the same work as this one. Do not use them as a price guide for this job.