This bid is for an HVAC controls upgrade at Pemberton Elementary School, 1300 Pemberton Drive, Salisbury, MD 21801.
Due
December 22, 2026
31 days left
Location
Salisbury, MD
Maryland
Posted on
Bonfire
Notice ID
91036-271
Please quote a fully integrated BACnet building automation controls upgrade, replacing the existing Network 8000 controls, at Pemberton Elementary School, 1300 Pemberton Drive, Salisbury, MD 21801.
System: Replace Network 8000 controls with a BACnet system, including demolition, hardware, wiring, installation, and programming.
Equipment: Controls for 2 boilers, chilled/hot water systems and pumps, 2 AHUs, 46 VAVs, 4 RTUs, 8 unit ventilators, 5 fan coil units, domestic hot water, kitchen ventilation, and Area A/B ventilation.
Field devices: New sensors and all new valve and damper actuators; valve actuators proportional, Schneider MS51-7103-105 or equivalent; inspect ATC valves and repack leaking ones.
Integration: New BACnet/IP network, existing lighting integration, Mazevo/events2HVAC scheduling, updated graphics, email alarms, and at least one month of trend storage.
Closeout: Commissioning, energy modeling and utility incentive support, on-site training, as-built documents, and a two-year workmanship and material warranty.
Schedule: On-site work in summer 2027, finished by August 26, 2027, Monday to Friday, 7:00 AM to 4:00 PM.
Please confirm availability and send your quote by December 22, 2026.
The original documents
Deadline: December 22, 2026
See the original on wicomicoschools.bonfirehub.com
Bidding it yourself? Get the full package and submit on Bonfire before December 22, 2026.
What they need
SystemReplace the existing Network 8000 controls with a fully integrated BACnet BAS, including demolition, hardware, wiring, installation, and programming.
EquipmentControls for 2 boilers, chilled/hot water systems and pumps, 2 AHUs, 46 VAVs, 4 RTUs, 8 unit ventilators, 5 fan coil units, domestic hot water, kitchen ventilation, and Area A/B ventilation.
Field devicesInstall new sensors and replace all valve and damper actuators. Valve actuators must be proportional, Schneider MS51-7103-105 or equivalent. Inspect ATC valves and repack leaking valves.
IntegrationNew BACnet/IP network with shielded input wiring, existing lighting integration, central BAS commands, Mazevo/events2HVAC scheduling, updated graphics, email alarms, and at least one month of trend storage.
CloseoutInclude commissioning, energy modeling and utility incentive support, on-site training, as-built documentation, and a two-year workmanship/material warranty.
Separate pricingProvide a lump-sum quote with itemized costs; separate options for temperature/RH/CO2 sensors, dehumidification/DCV sequences, and B-Wing dehumidifier integration. Include unit rates for valve repacking and valve body replacement under 2 inches and 2 inches or larger.
ScheduleAll on-site work must occur during summer 2027, with completion by August 26, 2027. Standard access is Monday–Friday, 7:00 AM–4:00 PM.