- ScopePhased replacement of 33 telemetry cabinets, including removal, disposal, mounting, field wiring, and replacement of corroded rigid conduit and explosion-proof seal fittings.
- CabinetsSP Manufacturing LLC LFS-3167 and LFS-3170 units; no substitutes. Outdoor enclosures must be NEMA 4X, 14-gauge 316 stainless steel with sunshields and 316 stainless steel mounting hardware.
- ControlsAllen-Bradley CompactLogix 5069 PLCs with Ethernet/IP, surge protection, and Tycon 24VDC passive PoE supplies compatible with existing Rajant radios. Battery backup must support four hours at full load.
- CompletionInclude factory testing, programming, SCADA integration, loop checks, calibration, startup, operator training, as-built drawings, and a one-year equipment and installation warranty. Maintain existing operations during replacement.
- Schedule and pricingWork will be phased over three years, with an optional additional year. Provide pricing by cabinet location and a separate mobilization/demobilization price.