Compressor: Replace one failed grounded ZP137KCE compressor with a new manufacturer-approved unit; field verify compatibility and include one new liquid-line filter drier and required circuit cleanup.
Condenser coil: Replace with a new manufacturer-approved coil with a corrosion-resistant coating that preserves its warranty.
Hail guard: Install a compatible Carrier-approved louvered kit; reference part CRLVHLGD032A00, subject to field verification.
Complete service: Include labor, materials, crane/rigging, access coordination, refrigerant recovery and charging, leak testing, evacuation, heating/cooling verification, disposal, and service documentation.
Schedule and warranty: Complete within 90 calendar days of the project start meeting, with active repairs and testing within 15 working days; provide a two-year workmanship warranty and standard component warranties.
Site visit: Mandatory walkthrough October 26, 2026, at 10:00 AM; arrive 15 minutes early and coordinate access.
Qualifications and pricing: California C-20 license, DIR registration, and EPA Section 608 Universal-certified refrigerant technicians required. Include prevailing wages and all applicable permits, taxes, insurance, and bonds in your lump-sum quote.