This bid is for fire alarm repairs, maintenance, and emergency lighting modernization at Buildings 20, 21, and 1000, Joint Forces Training Base, 11200 Lexington Drive, Los Alamitos, CA 90720.
This bid has closed.
Buyers often post the same work again. Set an alert below and we will email you when a similar California bid is posted.
What the job is
Building 20: Replace standby batteries sized for 24-hour standby plus 15-minute alarm operation; verify primary power; reprogram and test 13 smoke/CO detectors; test waterflow and valve supervisory interfaces; install a Honeywell HON-CGWMBB CLSS cellular communicator or approved equal.
Building 21: Replace one smoke/heat detector and one manual pull station, integrate programming, and verify existing monitoring connectivity.
Emergency lighting: Replace failed emergency lights, exit signs, bug-eye units, and ballasts in Buildings 20 and 21; verify 90-minute battery-backed operation. Quantities require site verification.
Annual service: Complete Building 1000 baseline inspection/testing, then provide 12 months of NFPA-compliant inspection, testing, and maintenance for all three buildings. Include 24/7 UL-listed central-station monitoring and communication costs for Buildings 20 and 1000.
Callbacks: Price separately by building; emergency response requires acknowledgment within 30 minutes and arrival within one hour.
Schedule and warranty: Complete initial work within 120 calendar days of the start meeting; include a two-year workmanship warranty.
Site visit: Mandatory walkthrough October 20, 2026, at 10:00 AM Pacific; arrive 15 minutes early to verify equipment and quantities.
Pricing: Provide itemized pricing by building, including labor, materials, equipment, permits, disposal, and applicable prevailing wages. An active California C-10 license is required.