This bid is for underground fuel tank inspection and testing at fuel sites throughout North Carolina, including the equipment depot at 5105 Beryl Road, Raleigh, NC 27606.
This bid has closed.
Buyers often post the same work again. Set an alert below and we will email you when a similar North Carolina bid is posted.
What the job is
Term and coverage: Three years of annual and triennial services statewide; the location list includes 119 gasoline and 124 diesel product lines.
Annual services: Overfill prevention checks with drop-tube removal, leak detection equipment testing, and sump visual inspections.
Triennial services: Single- and double-wall spill bucket, containment sump, piping primary and interstice, and tank interstice integrity testing. Include test-water removal and disposal.
Testing requirements: Certified technicians and calibrated equipment, including Veeder Root ATG certification where applicable. Tightness testing must detect 0.1 gallon per hour; line testing must use 1.5 times operating pressure.
Reporting and response: Completed inspection reports, online access to test records, due-date tracking, and emergency testing within 24 hours for suspected leaks or 48 hours for other emergencies.